Copyright © Yokogawa Electric Corporation June 2012 Yokogawa Electric Corporation YOKOGAWA VIETNAM CO.LTD SERVICE DEPARTMENT... of stations per HIS : Human Interface Station FCS : Fiel
Trang 1Copyright © Yokogawa Electric Corporation
<1/7/2011>
June 2012
Yokogawa Electric Corporation
YOKOGAWA VIETNAM CO.LTD
SERVICE DEPARTMENT
Trang 3Lunch: 12:00 – 1:00 pm Session Resume: 1:00 – 3:00 pm Tea Break: 3:00 – 3:15 pm
Sessions Ends: 4:00 pm
CENTUM VP Engineering Course
Trang 4Project Common Definition
Day 1
CENTUM VP Engineering Course
FCS Configuration I/O Module Configuration Software Switches Configuration Message Configuration
Control Drawing Builder
Day 2
Trang 5Day 3
CENTUM VP Engineering Course
Course Contents
HIS Configuration Window Configuration
Day 4
Graphic Builder
Day 5
Trang 7Dual redundant Token-passing bus for our DCS since 1975 as
reliable & robust control bus
• 20,000 + systems have been installed worldwide
37 years History and the continuity
Trang 9Max no of stations 256
Max no of stations per
HIS : Human Interface Station FCS : Field Control Station BCV : Bus Converter
CGW : Communication Gateway
YOKOGAWA VIETNAM CO.LTD
SERVICE DEPARTMENT
Trang 10– CENTUM VP is applicable for various types of applications and for various system architectures
– Seven 9’s (99.9999959) hardware availability
– Pair & Spare technology to keep higher control loop availability
– Intuitive look & feel HMI design
– The latest technologies can be applied in the control systems
– Easy integration with other subsystems
Trang 11Copyright © Yokogawa Electric Corporation
<1/7/2011>
CENTUM VP System Configuration - Overview
-Vnet/IP: Real-time Control Network -Ethernet: Information Network
-Exaopc: OPC Server
- Exaquantum : Plant information management system
Operator Station (HIS)
Field Network
Dual Redundant Vnet/IP
Real-time Control Network FCS Sub system gateway
Open Display Style Console HIS
Enclosed Display Style Console HIS
ESD / F&G
Client PC
Safety Instrumented System Controller
OPC server Exaopc
ProSafe-RS SENG
TSE server and/or ENG
Desktop type HIS PRM
ProSafe-RS SCS
Unified Gateway Station (UGS)
Ethernet Plant Information
Management System Exaquantum 3rd party wireless gateway
3rd party Sub systems STARDOM
Asset management
station
for FF/HART devices
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 13Plant Resource Manager (PRM)
the field devices but specifically the “intelligent” devices such as those with
either HART or Fieldbus communication.
devices more than a standard control system can do Maintenance personnel use this tool to see the health of the field devices It constantly monitors all of the devices on a periodic basis which is user defined.
work with PRM A valve “plug-in” is calibration software which allows the custom set up of the individual valve This allows the software to calibrate the valve around the specific dynamics and responses of the valve.
replacement of the device.
Trang 14This provides OPC Server functions to enable applications in a supervisory
PC to access CENTUM VP data This provides a links between control layer and business data processing layer.
Trang 16GSGW, APCS & Router
Advanced Process Control Station (APCS)
An APCS advanced process control station implements control functions with a general-purpose PC connected to a Vnet/IP, aimed at improving advanced control and plant efficiency.
Generic Subsystem Gateway Package (GSGW)
With a general –purpose PC connected to Vnet/IP, GSGW packages can collect and set various type of data from subsystem using an OPC DA server They can easily connect and set subsystem data without creating dedicated communications programs.
Router
A router with security function to ensure the security of a Vnet/IP network
is used to connect the bus 2 side with an external network such as Intranet.
Trang 18 Various types of the operation views are prepared
One-touch operation for related information
– Alarm dialog, trend graph, Graphics, and faceplates can be called up from each other based on the related tag without engineering
Ex Click alarm message then the related faceplate is shown
Large Capacity
– Max No of Tags: 1,000,000 per system
– Real-time trend Points: 3,328 per HIS
are available
– Single, dual, Quad LCD are available.
– Wide monitor is also available.
– Operation keyboard and touch screen are also
available
Real-time Alarm Management View
Features of HIS (Operation Station)
Trang 19Solid Style Console
Windows 7, VISTA, and 2008 server
Desktop, Solid Style Console and Open Style Console
Mouse/Operation Keyboard/Touch panel
Single, Dual and Quad-monitor are available
Open Style Console
Open Style Console
Desktop Type
Desktop Type
HIS Hardware
Trang 21Copyright © Yokogawa Electric Corporation
<1/7/2011>
Display Lay-out of HIS
Windows Desktop = Whole Area of CRT
System Message Banner = Alarm Display Area
Browser Bar = Navigation Tool
Container Window = Container Window or Pop up Window
* Frame = An element of Container Window
* Tab = Switches display
* View = An element of Frame or Pop Up Window (R3 HIS Window)
YOKOGAWA VIETNAM CO.LTD
SERVICE DEPARTMENT
Trang 22Copyright © Yokogawa Electric Corporation
<1/7/2011>
Examples of Frames and Pop-Up Window
System Message Banner
Trang 25grouped by function
Operation Keyboard Features
Trang 27Copyright © Yokogawa Electric Corporation
<1/7/2011>
Field Control System
I Process Control Functions
Four Types of FCS to choose from, for Flexible System Configuration: FIO, FCS for RIO, Compact FCS for FIO, and Compact FCS for RIO, according to your
application requirements, for system expansion or replacement.
KFCS/KFCS2
(Standard/Enhanced)
FIO
LFCS/LFCS2 (Standard/Enhanced) RIO
PFCS (Compact) RIO
FFCS (Compact) FIO
Trang 30– Seven 9’s (99.9999959) hardware availability
– Pair & Spare technology for
higher control loop availability
– One controller handles 1,760 analog signals and 4,096 digital signals
– Various field digital protocols can be handled: Foundation Fieldbus, ISA100, PROFIBUS, Ethernet/IP, HART, etc
– Up to 13 extra I/O racks
– Up to 50km distance remote I/O rack
– Regulatory Control blocks, Sequence Control Blocks, Arithmetic blocks, etc
– 7,000 functions work on a controller
– All the control application runs in the highly reliable controller hardware
FCS (Field Control Station)
Trang 31FCS (Field Control Station)
Address setting on the backside of the
FCS (CPU card)
Trang 34All data are equalized in real time without
affecting the control communication among
all HIS’s
Dual Power
Dual ESB/ER bus
Dual I/O modules
Analog, Digital, Fieldbus, Serial
Redundant Configuration of CENTUM VP
Trang 35 Both CPU modules are processing independently, so CENTUM achieves
real bumpless switchover (For Redundancy purpose)
A p air of CPU chips is on each CPU module
– Each CPU is processing independently
• This is not for redundancy purpose
Result c hecking
– Processed results of CPUs are every time compared each other – If the results are not congruous, control switches to the stand-by module (To avoid the effect of transient error)
Vnet/IP I/F
Power card Power card
Coupler Coupler Vnet/IP
IO bus I/F
CPU 1 CPU 2
CPU 1 CPU 2
PIO I/F PIO I/F
Vnet/IP I/F Main
memory
with
ECC
Main memory with ECC
Pair & Spare CPU Architecture
Error-Correcting Code repairs transient bit inversion errors
Trang 36– Almost 200 types of function blocks.
– Regulatory Control blocks, Sequence Control Blocks, Arithmetic blocks, etc.
– Any types of function blocks can work in a controller at the same time
– Control logics are generated by the combination of function blocks
– The processing period can be specified for each function block: 1-sec, 500-msec, 250-msec, 100-msec, and 50-msec can be chosen
Control Function
Trang 37Copyright © Yokogawa Electric Corporation
<1/7/2011>
Proprietary info goes here…
Control Network (Vnet/IP)
Vnet/IP is the control network that incorporates general communication func tion without losing highly reliable, real-time, and stable communication
1G bps Ethernet based control network
Being published by IEC as industrial communication standard PAS
Open
time Reliable
Real-YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 38neral Ethernet equipment
rs (Layer 2 switches and Layer 3 switches)
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 39Copyright © Yokogawa Electric Corporation
<1/7/2011>
Proprietary info goes here…
Vnet/IP Network Configuration
Trang 40HIS/ENG Open Vnet
HIS Open Vnet
PIMS Open
3rd Pty Appl Open
FCS
Vnet
PLC
Open Field Eye
Server
Open
GSGW Vnet Open
Vnet/IP – 1 Gbps Control Network
Open Communication (TCP/IP)
Control Communication (Vnet Protocol) Control Communication (Vnet Protocol) LAN2 cable
LAN1 cable
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 41Copyright © Yokogawa Electric Corporation
<1/7/2011>
Vnet/IP Features (bandwidth partitioning Control)
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Open
Communication
Spare for Control
Communication Backup
In case of errors in BUS 1, control is shrift to BUS 2
Trang 43Station 24
Network Address:
BUS 1: 172.16 3.24 BUS 2: 192.168.131.48
Station 34
Network Address:
BUS 1: 172.16 2.34 BUS 2: 192.168.130.68
Alternate Addressing for BUS 2: 192.168.[128+DD]
[128+DD+SS]
Trang 46One I/O node has 8 I/O module slots
I/O nodes are connected by the remote I/O bus (ESB Bus)
– Up to 10 m from the FCS CPU node to the end of the I/O node if electric cables are used as the ESB bus
– Up to 50 km in case of optical cables as the ESB bus
Max 9 I/O nodes/Line Total Max 13 I/O nodes (without CPU node)
CPU node
I/O node
Trang 47Eight FIO slots
EC401 ESB bus coupler(Note)
Note: Two I/O slots are to be used for NIU extension AIP504 VnetIP coupler (10BASE2 VnetIP cable is used.)
Detachable bottom unit
Centum VP Compact type
System Specification (FFCS)
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 48Copyright © Yokogawa Electric Corporation
<1/7/2011>
Page.48
VRAM,
16000000 colors can be specified.
80GB HDD (recommended minimum)
Video memory (512 MB minimum)
Page.48
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
HW/SW Requirement: Software
Trang 49YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 50Copyright © Yokogawa Electric Corporation
<1/7/2011>
1 Virtual Test Function
simulates the functions and operation of the FCS and runs under an HIS
Trang 51Tag01 PID
I/O simulator HIS01XX
Trang 52Review the I/O list, process control methods
and necessary hardware.
Basic Design
Using organized and structured windows to realize the desired control functions (regulatory control, sequence control and unit supervision) and the operation and monitoring
functions.
Detailed Design
Design detailed items (program configuration, creation of data list) for the regulatory control, sequence control, unit supervision and the operation and monitoring windows
according to the basic design.
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 53Using the actual FCS, check the overall validity
of functions and execution timings that were checked individually through the unit test.
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 54Expansion and Modification
Expand the station, as well as add and
change functions.
Review the I/O list, process control methods
and necessary hardware.
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 551 Start System View
Start Programs YOKOGAWA CENTUM System View
Trang 56Start Default Project Creation
When the System View could not identify an existing current or default project, it will prompt the user to create a default project with the dialog box
as shown below Click [YES] to create the default project
Trang 58Project name is an alphanumeric character string less than 8 characters
The comment within 32 alphanumeric characters or 16 double - byte characters may be entered as the project description
Moreover, an alias can be created for a project An alias of project can be defined with
8 alphanumeric characters
Trang 60Creating a HIS folder
A folder for the first HIS database files is created when the default project is created Assign the correct station type and station address as they cannot be modified upon confirmation Additional HIS can be created in future for more HISs
Trang 61The project consists of 3 basic folders – Common, FCS and HIS
Additional FCS, HIS or other stations can be created under the pull down menu Select project Right click on project Create New HIS or FCS
Trang 62YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 63 The Project’s Attribution Utility is an engineering tool that
makes it convenient to register a project created from other
PC, to change a project’s properties or to remove the registration of a project.
Before using the Project’s Attribution Utility, check that the
System View is not running If it is running, the Project Attribute Change Utility cannot run.
Only one project can exist as default project or current project in System View
Trang 64When any one of the FCS’s created in default project is successfully downloaded,
the attribute changes to a current project.
Created the first time when the
-Virtual test with the FCS
Can be downloaded to the FCS
Multiple projects can be created
Trang 65YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 66Project’s Attribution Utility
To change the Attribute of a Project
To remove a Project from System
View
Trang 68Exercise
Trang 69Project Common Item Definition
Station Configuration Viewer
Security Builder
Operation Mark Builder
Engineering Unit Symbol Builder
Switch Position Label Builder
Alarm Builder
Alarm Priority Builder
Alarm Processing Table Builder
System Fixed Status Character String Viewer
Trang 70Copyright © Yokogawa Electric Corporation
<1/7/2011>
From the System View
Project Common Item Definition
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 71Copyright © Yokogawa Electric Corporation
<1/7/2011>
Station Configuration Viewer
The Station Configuration Viewer displays the overview of the station configured for the project and a print out can be generated However, modification to the configuration is not allowed in this viewer
Project Common Item Definition
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
Trang 72Copyright © Yokogawa Electric Corporation
<1/7/2011>
Security Builder
Project Common Item Definition
YOKOGAWA VIETNAM CO,LTD
SERVICE DEPARTMENT
The security policy is set to prevent illegal operations and other problems and ensuring the safety of the system.
Trang 73is set to prevent illegal operations and other problems and ensuring the safety of the system
Trang 75Copyright © Yokogawa Electric Corporation
<1/7/2011>
Security Builder – Window Monitoring
YOKOGAWA VIETNAM CO.LTD
SERVICE DEPARTMENT
Trang 76Copyright © Yokogawa Electric Corporation
<1/7/2011>
Security Builder – Window Operation
Users with S3 rights can write data to Block mode,
SV and MV, but users with S2 rights cannot write
data to Block mode, SV and MV.
YOKOGAWA VIETNAM CO.LTD
SERVICE DEPARTMENT
Trang 82Operation Mark Builder
Trang 83Operation Mark: Privilege level & Color
Tag Level write access right on function blocks can be changed
Colors:
The following colors maybe used
on operation Marks and maybe temporarily changed on the HIS
Setup window
Privilege Level:
The privilege level required for a
user to attach/remove the
operation mark